What happened
On November 25, 2026, the US Cybersecurity and Infrastructure Security Agency (CISA) added three flaws in Danfoss AK-SM 800A devices to its catalog of exploited vulnerabilities. These are system managers that control and monitor refrigeration and other building equipment, typically in grocery stores and supermarkets. On the same day, the European vulnerability database EUVD, run by ENISA, also flagged them as exploited.
These are not new bugs. Two of them (CVE-2023-25915 and CVE-2023-25914) appeared in the NVD database on August 21, 2023. For these, CISA points to Danfoss advisory DSA-2023-08-01. The third (CVE-2025-41450) was published in NVD on May 8, 2025, and its record links to Danfoss advisory DSA-2025-03-01.
It is not unusual for old flaws to land in an exploited catalog years later. Attackers like to go after devices nobody has updated in a long time. Neither CISA nor ENISA has said who is exploiting the flaws or how widely. CISA does not yet know whether they are used in ransomware attacks.
Why it is dangerous
CVE-2023-25915 is the most serious. The device does not properly check the data it receives, so according to NVD a logged-in attacker can remotely run arbitrary commands. Think of a clerk who carries out everything written on a form, even when someone scribbles “and open the safe” at the bottom. The attack works over the network, but the attacker needs an account with at least basic privileges.
CVE-2023-25914 is a so-called path traversal. A logged-in attacker can use the XML interface to read system files they should never see, like changing the shelf number on an archive request slip and getting a folder from a locked room. NVD notes that the information obtained this way can lead to full system compromise.
CVE-2025-41450 is an authentication flaw in versions prior to 4.2. It does not require a login, although its CVSS rating says the attack is harder to pull off and needs some user action.
CVSS is a severity scale from 0 to 10. CVE-2023-25915 scores 9.9 and CVE-2023-25914 scores 8.8, both rated by the Dutch team DIVD (Dutch Institute for Vulnerability Disclosure). CVE-2025-41450 scores 8.2. That score comes not from NVD but from another organization that the record does not name.
The CISA KEV catalog lists flaws that CISA knows are being exploited in the real world. EPSS estimates the probability of exploitation in the next 30 days: as of November 25, 2026, it was 1.4% for CVE-2023-25915, 1.1% for CVE-2023-25914 and 0.5% for CVE-2025-41450. When exploitation is confirmed, a KEV listing matters more than a low EPSS score.
A compromised device could let an attacker change refrigeration and alarm settings. If it is connected to the company network, it could also serve as a stepping stone to other systems.
Who is affected
This affects anyone running Danfoss AK-SM 800A devices, also referred to in the NVD record as AK-SM 8xxA. For CVE-2025-41450, NVD lists all versions prior to 4.2. The NVD and CISA records do not give exact versions for the two 2023 flaws. For these, CISA points to Danfoss advisory DSA-2023-08-01.
Typical sites are supermarkets, grocery stores and cold storage warehouses, as well as other operations with controlled refrigeration. The device is often managed by an outside service company with remote access, and the business owner may not even know it exists. The biggest risk is where its web interface is reachable directly from the internet.
The NVD and CISA records mention only the AK-SM 800A series. If you use other Danfoss devices, check their status in the vendor’s security advisories.
How to check if you are affected
You can find the software version in the device’s web interface or in the tool your service company uses to manage it, usually under system information. If you have no access to the device, ask your service company in writing for the model, the software version and where the device can be reached from.
It is just as important to find out whether the device is reachable from the internet. Check your router or firewall for port forwarding rules pointing to its IP address. From a computer outside your network, for example over mobile data, you can test whether a web interface responds on your public address. These commands change nothing. Use them only on your own addresses.
curl -skI https://YOUR_PUBLIC_IP/
nmap -Pn -p 80,443 YOUR_PUBLIC_IP
If you get a response and it turns out to come from the Danfoss device, treat this as your top priority.
How to fix it
CISA requires US federal agencies to apply mitigations per the vendor’s instructions by November 28, 2026 for CVE-2023-25915 and CVE-2023-25914, and by December 9, 2026 for CVE-2025-41450. It also points to its BOD 26-04 directive and its forensics triage requirements. If mitigations are not available, CISA says to stop using the product. These deadlines are not binding for European businesses, but they show how urgent this is.
- Restrict access right away: remove any port forwarding from the internet to the device and allow remote access only via VPN or from specific addresses of your service company.
- Before making changes, save the device, firewall and VPN logs so you do not lose traces of a possible attack.
- Read Danfoss advisories DSA-2023-08-01 and DSA-2025-03-01 and find out which version fixes all three flaws.
- Update the device software. For CVE-2025-41450, NVD indicates version 4.2 or later. The update is usually done by the service company, so schedule it as soon as possible and ask for written confirmation of the new version number.
- After the update, change the passwords of all accounts on the device and remove accounts nobody uses.
- If a fix cannot be applied to your device, keep it fully disconnected from the internet in a separate network segment and consider replacing it.
Coordinate every step with your service company so you do not disrupt the refrigeration.
What if you may already be compromised
The CISA and NVD records do not list specific indicators of compromise, such as attacker IP addresses or file names. You therefore need to look for general signs.
- unknown or new user accounts on the device,
- changes to refrigeration, alarm or user settings that neither you nor the service company made,
- logins from unfamiliar addresses in device, firewall and VPN logs,
- outbound connections from the device to unknown addresses,
- unusual behavior of other systems on the same network.
Bring in an incident response specialist if a device running a vulnerable version was reachable from the internet, if you find any of the signs above, or if it sits on the same network as office computers and servers. Do not reset the device before it has been examined, or you may lose evidence.